YVZ4V-U ,YVZ4V-R, NYBY

Place of use

Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage. 

Structure

  • Solid or stranded copper conductor.
  • PVC insulation.
  • Filler.
  • Galvanized round steel wires.
  • PVC outer sheath.

Product Code Dimension and Weights Electrical Properties
Nominal Cross Section Overall Diemeter
( ~ )
Net Weight
( ~ )
Standart Lenght Max. Dc Conductor Resistance at 20◦ C Current Carrying Capacity
In Ground at 20° C On Air at 30° C
28-30000001 3x1.5 13.0 320 1000 12.1 26 18,5
28-30000002 3x2.5 14.0 380 1000 7.41 34 25
28-30000003 3x4 16.0 500 1000 4.61 44 34
28-30000004 3x6 17.0 600 1000 3.08 56 43
28-30000005 3x10 19.5 800 1000 1.83 75 60
28-30000006 3x16 21.5 1050 1000 1.15 98 80
28-30000007 3x25 25.0 1500 1000 0.727 128 106
28-30000008 3x35 27.0 1850 1000 0.524 157 131
28-30000009 3x50 31.0 2450 1000 0.387 185 159
28-30000010 3x70 35.0 3300 1000 0.268 228 202
28-30000011 3x95 40.5 4650 1000 0.193 275 244
28-30000012 3x120 44.0 5600 500 0.153 313 282
28-30000013 3x150 48.5 6800 500 0.124 353 324
28-30000014 3x185 53.5 8300 500 0.0991 399 371
28-30000015 3x240 60.5 10600 250 0.0754 464 436